PRIMST Low-Temperature Room Air Conditioner · Fault Code Quick Reference
Restructured from "Common Fault Codes & Remedies 2026.4.11" · Works offline
40Fault code
26Field-fault wording
7Fault category
17LED Reverse Lookup
🩺 Fault Lookup
💡 LED Reverse Lookup
🗂 Browse by Category
📡 Troubleshooting Flow
📋 Full Code List
🌡 Sensor Resistance
Category
Location
Shutdown?
matches 0 fault codes
Select a fault code
Click a code to see the exact remedy · codes marked with tag have LED flash data.
Remedy
Cause → Corrective Action + Ordered on-site steps
How to use:There are two fault indicators on the outdoor main board — Red LED5 and Green LED6,
During a fault theyflash alternately. First count the red flashes, then the green flashes, select the matching counts below, and you can identify the Fault code.
(Example: red 9 flashes + green 3 flashes = 93 compressor stall)
Number of red LED5 flashes
Number of green LED6 flashes
When both are set to "Any", the table below lists all 17 codes that have LED flash data.
Lookup Result
LED flash cross-reference table
Can be used directly on site as a lookup reference.
Browse by fault category
total 0 items · each card shows that code's "Primary fix"; click to view the full remedy
Applies to codes:00 Wired controller communication fault · 03 Outdoor unit communication fault · 90 Compressor drive communication fault ——
These three also have a quick-jump link at the bottom of their detail pages. All“indoor and outdoor units cannot communicate”communication troubleshooting can follow this flow.
Full Fault Code List
total 0 items · click a column header to sort, click a row to see the remedy.
How to use on site:When troubleshooting sensor-type faults (31/32/35/36/37/21/22/25/26/56, etc.),
measure the sensorResistance → look it up herecorresponding temperature → with theactual temperature.
A deviation of more than about 2℃ meansResistance drift, so the sensor should be replaced. You can also look up the standard resistance from a known temperature.
⇄
Temperature–Resistance Reference Table
Full OEM parameter table; values between tabulated points are linearly interpolated.